Whispering Controllers




Heinen & Hopman Engineering BV has found the ultimate controller for a real silent fancoil chilled water system. With our knowledge of those systems, we saw the need for a controller which could turn an European based input signal (230 Vac, 50 Hz) into a USA based output signal (230 Vac, 60 Hz) and vice versa.

The fact that the frequency output of this controller can be adjusted means, in terms of sound, that the noise level of the fan can be reduced with 10dBa.

Furthermore the fan speed can be selected, not only with a change in voltage, but also with a change in frequency. This option also leads to a smoother operation of the fan.

DESIGN FEATURES

USER SELECTABLE FUNCTIONS

  • Temperature displayed in either fahrenheit or celcius degrees
  • Multiple fan selections (6 speeds)
  • Calibration of the fan speed
  • Calibration of the ambient temperature sensor
  • Setting of the high and low water temperature sensor
  • Setting of the high and low water temperature limits
  • Setting of the heater options
  • Continuous "ON" operation of the heater view mode displays
  • Blanking of display lights when desired

DISPLAY PANEL

  • Low voltage display panel offers optimum safety
  • Light sensor controls display brightness for day or night operation
  • Cabin temperature and set point temperature can be displayed
  • Display panel available in gold or silver plated, or any R.A.L. color

INSTALLATION

  • Modular components provide easy installation
  • Easy connections using polarized plugs (phone / computer type)
  • All cables are shielded and grounded to protect against frequency interference
  • Also available a slave modules
  • NEW : The FC 1000 HD, which has a maximum load ventilator rev. control of 5.0 AMP


Fancoil Controller - FC 400 HP


SPECIFICATIONS
 
MODEL
VOLTAGE
FC 400 HP
115 Vac¹ / 230 Vac
50/60 Hz


CIRCUIT PROTECTED FUSES
 
Internal Transformers
Fan
Heating
Water Valve
1.0 Amp. slow
5.3 Amp. slow
10.0 Amp. slow
5.0 Amp. slow


TEMPERATURE RANGES
 
Set Point Temperature
Display Temperature
Air Sensor Temperature
Water Sensor Temperature
13°C - 29° C
- 18°C - 66° C
- 18°C - 66° C
- 18°C - 66° C
55°F - 85° F
0°F - 150° F
0°F - 150° F
0°F - 150° F


With Variable output frequency³
1 - 20Hz - 93 Vac
2 - 23Hz - 106 Vac
3 - 27Hz - 121 Vac
4 - 31Hz - 144 Vac
5 - 38Hz - 177 Vac
6 - 50Hz - 226 Vac


With fixed output frequency - 50 Hz³
1 - 93 Vac
2 - 106 Vac
3 - 121 Vac
4 - 144 Vac
5 - 177 Vac
6 - 226 Vac


MAXIMUM LOAD FAN REV.CONTROL:2.18 Amp(4)


DIMENSIONS
 

Controller WxHxD
Display Panel (WxHxD)
Cable Lengths
 
 
 
 
- Display
- Air Sensor
- Water Sensor
132 x 153 x 115 mm
102 x 102 x 44 mm
4400 mm
2200 mm
2200 mm


  1. Optinal
  2. With a supply voltage of 230 Vac
  3. Unimpeded, when Impeded, the output voltages will be on average 5 Vac lower (dependant on the type of fan motor)
  4. Slave module, FC 400 SP, maximum load ventilator rev. control is 2.18 Amp

TOP