Airhandling Unit
Closed Marine  Central Unit

The closed Marine central unit is for a Single Pipe system supplying 5000 m³/h. It is a type 05 unit including sections for mixing, filtering, cooling, preheating, fan, reheating and sound trap.

The Closed Marine Central Unit as shown is a compact unit including the necessary sections such as mixing section, filter section, heating coil section, cooling coil section, humidifier section, fan section and sound traps.

Inspection doors and easily removable side plates secure good service possibilities. The sections are built together and mounted on a frame, ready for mounting onboard.

This central unit is supplied in a standard programme with dimensions as shown in the table below. These are 8 sizes from 1.360 m³/h up to 21,100 m³/h. The sketches show the various central units built up from the maximum possibilities of sections, but they can be supplied in any individual selection of sections. The dimensions are informative only and shall be confirmed in all actual cases.



Diagram - Air Handling Unit

Diagram - Air Handling Unit


Diagram - Air Handling Unit

Diagram - Air Handling Unit


Size Max.cap.m³/h H=B=LMmm LFa Ls standard lengths
01 1360 500 750 250 - 500 - 750
02 1820 560 800 250 - 500 - 750
03 2920 680 920 250 - 500 - 750
04 4270 800 1050 250 - 500 - 750
05 5900 920 1170 250 - 500 - 750
06 8810 1100 1340 250 - 500 - 750
07 13600 1340 1340 250 - 500 - 750
08 21100 1640 1640 250 - 500 - 750


Ventilation Systems

The Kombivent series of air handling units is ideally suited for ventilation systems.

These are a supply unit comprising a damper, filter, heater and fan and an extract unit consisting of a fan or fan and damper. When the air handling unit is inoperative the damper should be closed in order to protect the heating coil from frost and to prevent back draught through the system. Additional protection of the coil may be provided by the installation of an electric heater element within the unit.

The heating capacity should be sufficient to warm the incoming air to the desired temperature during the heating season. The supply fan draws in fresh air from the outside and distributes it through the ducting system; the extract fan removes the stale air from the ventilated area and discharges it from the outside.

Units may also be provided with an air mixing section so as to enable re-circulation or partial re-circulation of the air, if required.

Ventilation Systems with Cooling

This ventilation system can be extended by the addition of a section for cooling and/or dehumidification of the air. For this purpose, a chilled water cooling coil, led from a remote water chiller, is included in the unit. Alternatively a direct expansion cooling coil may be used, whereby the coolant, circulated by a remote compressor and condensing unit, evaporates within the coil.

Combined Systems

In combined systems, the supply ventilation unit and the extract fan are combined to form one air handling unit, by inserting a combined damper mixing section. This section not only enables air to be discharged but also to be re-circulated to supplement the outside air as required and reduce the heating load. The ratio of the two air quantities is adjustable.

Systems with humidification

To obtain complete air handling, the air handling unit can be extended to include humidification. Humidification can be affected by a diabatic humidification of the air by means of a water sprinkling device or a package humidifier. Humidification can also be provided by injecting steam into the air. With adiabatic humidification, the air should be pre-heated to enable it to absorb sufficient moisture, and to achieve satisfactory control should, in many cases, be re-heated because air cools down as a result of this humidification process.

The level of humidity can be regulated by switching the pump on or off, by adjustment of the water supply by means of a three-way valve, a multi-speed or adjustable speed pump motor. In case of steam humidifying, re-heating is not necessary because the required latent heat is already available in the steam.

Systems with Heat Recovery

For heat recovery from the discharge air, the following systems are available, the section being determined by the technical and economic requirements.

  • Rotorvent - Rotating heat wheel

  • Twinvent - Twin coil system (Run-a-round)

  • Direktvent - Plate type heat exchanger

  • Heatvent - Heat-pipe exchanger